GE Multilin G500 Instruction Manual page 83

Substation
Hide thumbs Also See for Multilin G500:
Table of Contents

Advertisement

G500 Substation Gateway
Appendix A: Standards & Compliance
Compliance Standards
TEST
Insulation Resistance Test
Dielectric voltage withstand
Impulse voltage withstand
Damped Oscillatory
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Radiated & Conducted Emissions
Sinusoidal Vibration
Shock & Bump
Seismic
Power magnetic Immunity
Voltage Dip & interruption
Conducted RF Immunity 0-150khz IEC 61000-4-16
Voltage Ripple
Ingress Protection
Environmental (Cold)
Environmental (Dry heat)
G500 SUBSTATION GATEWAY INSTRUCTION MANUAL
Standards & Compliance
The G500 complies with the tests listed below. The test methods covered, provide
compliance to IEC61850-3 Location H or G when equipped with a Low voltage power
supply (48Vdc) or High voltage power supply (full nominal range). The G500 is also fully
compliant to IEEE1613: Class 1.
REFERENCE STANDARD
EN 60255-27
EN 60255-27
EN 60255-27
IEC 61000-4-18
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
CISPR22 & CISPR32
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-17
IEC 60529
IEC 60068-2-1
IEC 60068-2-2
TEST LEVEL
500 Vdc
2.0 kV
5 kV
100kHz & 1Mhz 2.5kV CM, 1kV DM
Level 4
Level 3
Level 4
Level 3 & 4
Level 3
Class A
Class 1
Class 1
Class 2
Level 5
0,40,70,80% dips, 250/300cycle interrupts
Level 4
15% ripple
IP30
-40°C 16 hrs. (Storage and Operational)
60°C 16hrs for Quad Core
70°C 16 hrs. Dual Core
85°C 16 hrs. Storage (both models)
GE INFORMATION
83