DST 11000 = FL40A (MOV 11000 = FL40A for the S10V)
The TCD number (11000) is specified for the transparent message to be transmitted.
FLCM HE2800 (FLCM FW400 for the S10V)
The parameter storage address (HE2800 = FW400 real address) is specified for the
mathematical/logical function (FLCM). A message request (transparent-message
transmission) is issued to the FL.NET module.
[CPU02 or LPU02-side ladder program]
R101
R081
(00001)
The program runs when the transparent-message reception bit (R081) in the self-node status
flag is set and the node 1 reception bit (R101) in the transparent-type reception flag area is
also set. The program then checks the user-requested-processing-in-progress bit (R080) in
the self-node status flag (message processing can be performed when the user-requested-
processing-in-progress bit is reset.)
The parameters for transparent-message transmission are specified by mathematical/logical
functions.
DST 17 = FL400 (MOV 17 = FL400 for the S10V)
The message transmission service number is set to 17. A transparent-message reception
request is specified.
DST 1 = FL402 (MOV 1 = FL402 for the S10V)
A transparent message from the remote station (CPU01 or LPU01) is specified.
R080
V000
The description in parentheses is for the S10V.
5-111
17 = FL400
(MOV)DST
F
H1 = FL402
(MOV)DST
F
AST
RW090 = FL404
F
AST
FW000 = FL406
F
(MOV)DST
1024 = FL408
F
FLCM
HE2800(FW400)
F
5 USER GUIDE