5.5

Welding the Outdoor Unit Ports

5.6
(Optional) Connecting Low Temperature Component Pipes
To outdoor unit gas pipe
To indoor unit
liquid pipe
6

Connecting Water Pipes

Connecting the Humidifier Water Inlet Pipe

6.1
G 3/4 inch reserved connector
with outer screw thread
G 3/4 inch adapter with inner screw thread
Matched with the adapter, the pressure
resistance should be at least 0.7 MPa
Note 1:
1. When plastic materials such as PA66 are used, the recommended torque is 5 N.m.
2. When metal materials are used, the recommended torque is 10 N.m. A sealing washer must
be used when an union is used.
Thermal insulation foam
5/8 inch liquid pipe
7/8 inch gas pipe
To indoor unit gas pipe
1
Thermal
insulation foam
7/8 inch gas pipe
To outdoor unit liquid pipe
When the outdoor is installed vertically, the
gas pipe should be connected to the top
port and liquid pipe should be connected to
the bottom port.
A reducing pipe is required when welding
3/4 inch copper pipe to 5/8 inch connector.
13
5/8 inch liquid pipe