Huawei SUN2000-2KTL-L1 User Manual page 74

Hide thumbs Also See for SUN2000-2KTL-L1:
Table of Contents

Advertisement

SUN2000-(2KTL-6KTL)-L1
User Manual
Procedure
Step 1 On the home screen, choose Power adjustment > Grid-tied point control.
Figure 7-10 Grid-tied point control
Table 7-1 Grid-tied point control
Parameter Name
Active
Unlimited
power
Grid
connectio
n with
zero
power
Issue 03 (2020-07-20)
Description
-
If this parameter is set to Unlimited, the output power of
the SUN2000 is not limited and the SUN2000 can connect
to the power grid at the rated power.
Closed-loop
● If multiple SUN2000s are cascaded, set this parameter to
controller
● If there is only one SUN2000, set this parameter to
Limitation
Total power indicates export limitation of the total power
mode
at the grid-tied point.
Power
Specifies the shortest interval for a single anti-backfeeding
adjustment
adjustment.
period
Power control
Specifies the dead zone for adjusting the SUN2000 output
hysteresis
power. If the power fluctuation is within the power control
hysteresis, the power is not adjusted.
Active power
Specifies the derating value of the SUN2000 active power
output limit
by percentage. If the Smart Dongle does not detect any
for fail-safe
meter data or the communication between the Smart
Dongle and the SUN2000 is disconnected, the Smart Dongle
delivers the derating value of the SUN2000 active power by
percentage.
Communicatio
In the SUN2000 anti-backfeeding scenario, if this parameter
n
is set to Enable, the SUN2000 will derate according to the
disconnection
active power derating percentage when the communication
fail-safe
between the SUN2000 and the Smart Dongle is
disconnected for a period longer than Communication
disconnection detection time.
Communicatio
Specifies the time for determining the communication
n
disconnection between the SUN2000 and the Dongle.
disconnection
This parameter is displayed when Communication
detection time
disconnection fail-safe is set to Enable.
Copyright © Huawei Technologies Co., Ltd.
SDongle/SmartLogger.
Inverter.
7 Man-Machine Interaction
68