C
Power Cable Specifications
YJV5 cables are recommended. When the ambient temperature is 40º C, the conductor working
temperature cannot exceed 90º C.
Wiring
Rated
Terminal
Current (A)
160
250
Power input
(L/N)
400
630
160
250
Power input
(PE)
400
630
< 10
10 ≤ I ≤ 40
AC output (L)
40 < I ≤ 63
< 10
AC output
10 ≤ I ≤ 40
(N/PE)
40 < I ≤ 63
Cable
Terminal/Bolt
Diameter (mm² )
Specifications
50
DT-M10
95
DT-M12
185
DT-M16
2x150
DT-M12
25
DT-M10
50
DT-M10
95
DT-M12
2x70
DT-M12
Cord end terminal (plug
2.5
depth 8–12 mm)
Cord end terminal (plug
6
depth 8–12 mm)
Cord end terminal (plug
10
depth 8–12 mm)
2.5
OT-M6
6
OT-M6
10
OT-M6
Shenzhen 518129 People's Republic of China
19
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang
Recommended Torque
(N•m)
26–33
46–58
46–58
46–58
26–33
26–33
46–58
46–58
1.5–1.8
1.5–1.8
1.5–1.8
4.9
4.9
4.9
www.huawei.com