Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 20

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

1
DIAGNOSTIC AND MAINTENANCE
FUNCTIONS
This section explains the diagnostic and maintenance functions of the Windows part.
1.1
Watchdog Timer (WDT) Function
This function detects hardware errors of the Windows part of this product.
Watchdog timer types
The watchdog timers that run on the Windows part are as follows.
The watchdog timers of the Windows part and VxWorks part run independently. For the watchdog timers of
the VxWorks part, refer to the following page.
Page 98 Watchdog Timer (WDT) Function
Function name
Windows part
System watchdog timer
*1 Time-up errors may be detected from hang-ups of the user application.
Monitoring time setting
This section shows the method for setting a watchdog timer monitoring time.
System watchdog timer
A system watchdog timer can be set in "System WDT Setting" of "WDT(Watchdog Timer) Setting (Windows part)".
Window
[Basic Parameter]  [RAS Setting]  [WDT(Watchdog Timer) Setting (Windows part)]
Displayed items
Item
Monitoring time
1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
18
1.1 Watchdog Timer (WDT) Function
Description
Detects errors (system hang-ups, etc.) in the system programs of the Windows part stemming from
hardware abnormalities.
Description
Set the system watchdog timer monitoring time.
*1
Setting range
1 to 600 (s) (1 s units)
(Default: 5 s)