GE 1200 Series Interconnection And Wiring Manual page 13

Fire panels, repeaters, and emulators
Table of Contents

Advertisement

3.3.3
Relay outputs (Class B)
OUT1 / OUT2 / OUT3
Two configurations are available. The configuration is determined by jumper settings.
Figure 8: Two configurations for relay outputs 1-3 B (shown as not active)
Table 1: Relay configuration option for outputs OUT1, OUT2, and OUT3
Output
OUT1 (Sounders)
OUT2 (Fire brigade)
OUT3 (Fire protection)
OUT4
The configurations for OUT4 are shown below (failsafe). The switch is closed when there is a fault and
open when there is no fault.
Figure 9: Two configurations for relay output 4 B
Table 2: Relay configuration option for output OUT4,
Output
OUT4 (Fault routing)
Configuration 1
J12 in
J13 out
J2 in
J3 out
J4 in
J5 out
Configuration 1
J6 in
J7 out
1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
Configuration 2
J12 out
J13 in
J2 out
J3 in
J4 out
J5 in
Configuration 2
J6 out
J7 in
Comment
J18 out
J19 out
J18 out
J19 out
13