Commissioning
4.5 Establishing an online connection to the drive unit
4.5.3.2

Online access via PROFINET

Use online access
Get the TIA Portal to search for the drive via the online access of your computer.
Requirement
● You have inserted a CU320-2 PN Control Unit.
● There is a connection between the Ethernet interface of your PG/PC and the PROFINET
interface of your drive (X150).
Procedure via "Online access"
To search for a drive, proceed as follows:
1. Open the "Online access" entry in the project navigator.
2. Select the network interface of your computer.
3. Double click on "Update accessible devices".
The drive is displayed in the project navigator.
Figure 4-47
If the communication parameters are at their factory settings (IP address 0.0.0.0 and no
device name), then the default device names of the TIA Portal ("Node" in this case) and
the MAC address are displayed.
If you want to go online on the device, you must assign an IP address and a device
name.
142
PROFINET online access
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1