Error messages and troubleshooting
5.2 Error messages
Error code
(B#16#...)
52
Flashing of
ERR LED
19
25x
Previous command is active or buffer overflow.
The user sent a new command to the CM although the last command
was still active.
1A
PROFIBUS DP error occurred.
This error is only indicated when access monitoring has been enabled
in the PROFIBUS configuration.
1B
27x
Other application active (for example firmware download)
1C
28x
The antenna of the reader is turned off. A tag command to the CM was
started in this status.
1D
More transponders are located in the transmission window than can be
processed at the same time by the reader.
1E
30x
Error when processing the function
1F
Active command canceled by RESET (init_run) or bus connector was
unplugged
Active command can only be terminated with an init_run.
Before a new command can be started the READY bit must be 1
(exception: init_run).
Two FB 45 calls were assigned the same parameters
("ASM_address" and "ASM_channel").
Two FB 45 calls are using the same Params_DB pointer.
Start init_run command after error correction.
When command repetition is used, no data is fetched from the tag.
The data buffer on the CM has overflowed. Tag data has been lost.
The PROFIBUS DP bus connection was interrupted
Wire break on the bus
Bus connector on CM was briefly unplugged
PROFIBUS DP master no longer addressing CM
Execute an init_run
The CM has detected a frame interruption on the bus. The
PROFIBUS may have been reconfigured (e.g. with HW Config).
Turn on the antenna with the "SET-ANT" command
The antenna is turned on (off) and has received an additional turn-
on (turn-off) command.
Only 1 tag can be processed at a time with FB 45
The data in UDT 10 are invalid (e.g. write command with length =
0); check UDT 10 and execute init_run
Hardware defect: CM receives wrong data with init_run.
The "number of bytes" byte does not match the user data length
(see Section "Programming the MOBY-ASM on PROFIBUS DP-
V1").
Communication with the tag was aborted by init_run.
This error can only be reported on init_run or cancel
Function Manual, 07/2012, J31069-D0166-U001-A4-7618