The description of the parameters visible on the display can deviate from the details in the
table in some cases due to the restricted number of available characters. The parameter
code is the most reliable means of reference.
M01 General
P01.01
P01.02
P01.03
P01.04
P01.05
P01.06
P01.07
P01.04
P01.07
7KT multimeter
Manual, 08/2018, 2514284149-01
Primary current of the cur-
rent transformer
Secondary current of the
current transformer
Nominal voltage
Rated power
Nominal voltage of primary
winding of voltage trans-
former
Nominal voltage of second-
ary winding of voltage trans-
former
Wiring configuration
• ON: Voltage transformers are used.
• OFF: The next two parameters will be ignored.
Set in accordance with the selected connection diagram.
Unit
Default
Range
A
5
1 ... 10000
A
5
1 ... 5
V
400
50 ... 500000
–
OFF
•
•
V
100
50 ... 500000
V
100
50 ... 500
–
L1-L2-L3-N
•
•
•
•
•
•
Description
3.4 Parameterization
OFF
ON
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
29