FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
Context
If the air conditioner implements cold-aisle control, install the T/H sensor on the door frame
of the IT cabinet front door. If the air conditioner implements hot-aisle control, install the T/H
sensor on the door frame of the IT cabinet rear door.
Procedure
Step 1 Secure the T/H sensor base to the 33 U position on the IT cabinet door frame using M5x10
tapping screws.
Step 2 Mount the T/H sensor onto the base.
Figure 7-67 Installing a T/H sensor
----End
Issue 04 (2017-06-30)
The installation position for the T/H sensor can be adjusted between 33 U and 40 U based on site
requirements.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Installing Monitoring Devices
169