Power Cable Specifications - Huawei PDU8000 Series User Manual

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000 Series:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
No.
6
7
8
9

5.4.2 Power Cable Specifications

YJV5 cables are recommended. When the ambient temperature is 40° C, the conductor
working temperature cannot exceed 90° C.
Table 5-7 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)
Issue 02 (2016-11-10)
Cable Layout Rule
Connection ports and cabling methods facilitate maintenance, cable
routing, and capacity expansion.
Cable connectors prepared onsite must be normal, secure, reliable, and
neat.
Power cables, ground cables, and various signal cables are securely
connected. Adapters are securely plugged or screwed.
The N and PE cables are bound separately from the L1/L2/L3 or L cables
for each circuit breaker. Cables are converged at the beam and bound in
groups by cable ties.
Rated
Cable
Current
Diameter
160 A
50 mm
250 A
95 mm
400 A
185 mm
160 A
25 mm
250 A
50 mm
400 A
150 mm
< 10 A
2.5 mm
10 A ≤ I ≤ 40
6 mm
A
40 A < I ≤ 63
10 mm
A
< 10 A
2.5 mm
10 A ≤ I ≤ 40
6 mm
A
40 A < I ≤ 63
10 mm
A
Copyright © Huawei Technologies Co., Ltd.
Terminal/Bolt
Specifications
2
DT-M10
2
DT-M12
2
DT-M12
2
DT-M10
2
DT-M10
2
DT-M12
2
Cord end
terminal (plug
depth 8–12 mm)
2
Cord end
terminal (plug
depth 8–12 mm)
2
Cord end
terminal (plug
depth 8–12 mm)
2
OT-M6
2
OT-M6
2
OT-M6
5 Installation Guide
Recommended
Torque
26–33 N· m
46–58 N· m
46–58 N· m
26–33 N· m
26–33 N· m
46–58 N· m
1.5–1.8 N· m
1.5–1.8 N· m
1.5–1.8 N· m
4.9 N· m
4.9 N· m
4.9 N· m
46

Advertisement

Table of Contents
loading

Table of Contents