Huawei NetCol8000-E220 User Manual page 79

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Menu
Issue 02 (2019-10-10)
Parameter
Teamwork
CAN resistor
Teamwork
function
Networking
mode
Number of
smart cooling
products in
this group
Number of
running smart
cooling
products in
this group
Rotation
function
Rotation
period
Rotation time
Forced rotation This item is set to No by
Requirement
control
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Setting Guide
for non-teamwork
scenarios.
For teamwork scenarios,
set this parameter to Yes
for the first and last
smart cooling products in
a teamwork group, and
set it to No for other
smart cooling products.
Set this parameter based on
the onsite device heat
distribution.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control
over a CAN bus,
MAC_CAN network
teamwork control over an
FE port.
Total number of the smart
cooling products in this
group.
The host allocates running
units by smart cooling
product unit address in
ascending order, which is
from 1 to 32. The rest will
become the standby ones.
This function is
recommended when the heat
is even.
7 by default
0 by default
default. If forced rotation is
required, the function is set
to Yes.
Anti-competitive running
is recommended for the
following scenario: In one
teamwork, the temperature
and humidity control type
and temperature and
humidity set point of units
Default Value
Disable
CAN network
3
2
Disable
7 day (s)
0
No
Disable
71

Advertisement

Table of Contents
loading