Huawei iBAT 2.0-CIM01C2 User Manual page 64

Hide thumbs Also See for iBAT 2.0-CIM01C2:
Table of Contents

Advertisement

iBAT 2.0-CIM01C2
User Manual
Step 2 Choose Monitoring > Control > System Commands and Tests, and click Start for
Capacity test.
Figure 8-2 Battery test
Step 3 Check the battery string current.
If the difference between the Str Cur (A) of each battery string and the measured battery
string current is less than 2% of the Hall effect sensor specification (for example, the
difference is less than 4 A for a 200 A Hall effect sensor), the system cable connections are
proper.
----End
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
8 Battery Test