Connecting Power; Connecting Low Dc Power - Siemens RUGGEDCOM RX1512 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1512:
Table of Contents

Advertisement

RUGGEDCOM RX1512
Installation Guide
Figure 4: Failsafe Alarm Relay Wiring
1. Normally Closed    2. Common    3. Normally Open
Section 2.5

Connecting Power

The RUGGEDCOM RX1512 supports a single low DC power source.
DANGER!
Electrocution hazard – risk of serious personal injury or death. Make sure the power source is off before
servicing the power terminal.
IMPORTANT!
• Use minimum #16 gage copper wiring when connecting terminal blocks.
• The maximum wire length between the terminal block and power source must not exceed 6 m (20 ft)
for 24 V power supplies or 18 m (60 ft) for 48 V power supplies.
• For 125/230 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• Equipment must be installed according to applicable local wiring codes and standards.
CONTENTS
Section 2.5.1, "Connecting Low DC Power"
Section 2.5.2, "Testing Dielectric Strength"
Section 2.5.1

Connecting Low DC Power

To connect a low DC power supply to the device, do the following:
Connecting Power
1
2
3
Chapter 2
Installing the Device
9

Advertisement

Table of Contents
loading

Table of Contents