42
PositionMaster EDP300 DIGITAL POSITIONER | CI/EDP300-EN REV. D
... 11 Supplemental specifications
Transmission data and contributing
factors
Output Y1
Increasing set point signal
Decreasing set point signal
Action (set point signal)
Increasing set point
Decreasing set point
Characteristic curve (actuator travel = f {set point signal})
Linear
Equal percentage 1:25 or 1:50 or 25:1 or 50:1*
Deviation
< 0.5 %
Configurable zone
0 to 100 %,
Configurable dead zone
0.1 to 10 %,
Resolution (AD-conversion)
> 16,000 steps
Sampling frequency
20 ms
Ambient temperature effect
< 0.5 % for each 10 K
Influence of vibration
Standard design:
Marine version:
*
freely configurable with 20 reference points
Seismic vibration
Meets requirements of DIN / IEC 60068-3-3 Class III for strong
and strongest earthquakes.
Influence of mounting orientation
Not measurable.
Noise emissions
Max. 100 db (A)
Noise-reduced version max. 85 db (A)
Change from two to one column
Increasing pressure at output
Decreasing pressure at output
= actuator position 0 to 100 %
= actuator position 0 to 100 %
< 1 % to 10 g and 80 Hz
< 1 % to 4 g and 100 Hz – EDP300 and
remote design (control unit) < 1 % to 10 g
and 100 Hz for remote design (position
sensor)
Ambient conditions
Ambient temperature range
During operation, storage,
and transport
0 to 100 %
*
Increased temperature range only with EDP300 Remote Sensor.
0 to 100 %
Relative humidity
During operation with housing
closed and air supply switched on
Transport and storage
4 to 20 mA
20 to 4 mA
12 Additional documents
Note
All documentation, declarations of conformity and certificates
are available in ABB's download area.
www.abb.com/positioners
−40 to 85 °C (−40 to 185 °F)
−40 to 100 °C (−40 to 212 °F)*
95 % (annual average), condensation
permissible
75 % (annual average)