Section 4
Protection functions
886
R
1
~
R
N
GUID-93DCB3EB-9200-4566-B4BF-54DBAF25AFE1 V1 EN
Figure 478:
The fault loop impedance model for phase-to-earth impedance
measuring elements
R
Positive-sequence resistance from measuring point to fault location
1
X
Positive-sequence reactance from measuring point to fault location
1
R
Earth return path resistance = (R
N
X
Earth return path reactance = (X
N
R
Zero-sequence resistance from measuring point to fault location
0
X
Zero-sequence reactance from measuring point to fault location
0
R
Physical fault resistance between phase and earth (includes arc and earthing resistances)
F
Considering the load in case of a single line-to-earth fault, conventional distance
protection might overreach at the exporting end and underreach at the importing end.
DSTPDIS has a load compensation functionality which increases the security in such
applications. Load compensation is enabled with the setting Load Comp zone x (x =
1...5) = "True".
Load compensation is used only with single phase-to-earth faults.
Load compensation is not used if multiple phases are included in the
fault (more than one single earth fault release).
X
+X
1
X
1
R
F
X
N
- R
)/3 from measuring point to fault location
0
1
- X
)/3 from measuring point to fault location
0
1
1MRS759142 C
X
N
R
F
R
+R
1
N
Technical Manual