Lon-Bus Devices - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

26

LON-Bus devices

26.1
Features
26.2
LON-Bus as stubline
Z1I030/050
E3I040
72
Fire & Security Products
Siemens Building Technologies Group
Activation via local communication Bus 'LON'
4 different types of device available
B3Q580
B3Q590/595 = Text control terminal
K3I050
K3I110
Connection via I-Bus/LON module E3I040 (converter between I-Bus and LON-Bus)
the function 'LON-Bus' is possible once per station type 'CI/'CT'' and 'CC'
max. 32 devices per LON-Bus (device type can be mixed as required)
monitored two-wire-Bus without loop line function
all devices require a separate feed line from E3I040
Wiring of the LON-Bus
as 'stub line' up to 1000m (without T-branches)
as 'free topology' up to 500m (length of line to all devices added)
with 'MICC' : as 'stub line' .....700m / as 'free topology' .....300m
with special cable (Belden 85102 or 8471) and as 'stub line' up to 2700m
only possible via twisted line (10 turns per meter)
CPU-overlapping functions possible
B3Q59x: bottom three LEDs are pluggable. Allows application with different LED colour.
E3X10.
or
B3Q...
E3I040
LON-Bus
Z1B070
= Text display terminal
= LON/Mimic Display converter
= LON I/O card
I-Bus
max. length of LON-Bus 1000m
24V
DC
K3I110
E3I040
K3R072
B3R051
K3I050
B3Q580
(not monitored)
Data bus
24V
DC
K3R072
Details see
or
page 70 or
B3R051
page 48
CC11
CI11
CT11
B3Q590/
595
K3R072
or
B3R051
e4595e 26
05.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents