Automatic refrigerant amount detection function

This function checks amount of refrigerant in the system through refrigerant amount detection operation
Press the Tact switch "K2" 5 times
Satisfy the temperature condition
Check the amount of refrigerant
Check stability
Yes
Connect S-Net Pro2
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal / Excessive /
Insufficient
❇ After refrigerant amount detection is finished, if you see "K9 Ed" on the display and cannot check the refrigerant
amount from the S-net pro and S-checker, it means insufficient degree of supercooling .
116
DVM S HE_IM_DB68-05461A-08_EN.indd 116
Start
Satisfy the temperature condition
Check the amount of refrigerant
No
Judge the amount of refrigerant
Judgment not
refrigerant: Normal / Excessive /
available
End
Input S-CHECKER signal
Check stability
Yes
Judgment on the amount of
Insufficient
No
Judgment not
available