High Temperature Linkage; Optional)Commissioning An Intelligent Aisle Light - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

6.3.2 High Temperature Linkage

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings>Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 Ensure that Link high temperature with skylight open is in on state on the Linkage Group
tab page. If it is in off state, set it to on.
----End
Follow-up Procedure
After the alarm has been cleared when high temperature linkage occurs, perform the
following operations:

6.3.3 (Optional)Commissioning an Intelligent Aisle Light

If the camera web version is earlier than IPC V200R003C00, commission the camera by
referring to this topic.
Prerequisites
The upstream power input circuit breaker of the AC actuator is turned on.
Context
After the intelligent aisle lighting is set successfully, perform the following steps:
Issue 05 (2019-09-16)
The ECC800 implements high temperature linkage. If it detects high temperature alarms
by interacting with multi-functional sensors and all smart cooling products fail to
communicate with the ECC800, the ECC800 opens skylights based on the alarm status to
facilitate heat dissipation.
The default status of high temperature linkage is off. Set it based on the actual situation.
Click Link high temperature with skylight open on the Linkage Group tab page. If it is in on state,
the corresponding logic configurations on the Linkage Logic List tab page are available. If it is in off
state, the corresponding logic configurations on the Linkage Logic List tab page are unavailable.
Close the skylights manually.
Start the smart cooling products manually.
After the door is opened using the access control system, the lighting is turned on.
In the smart module aisle, the lighting is turned on when a camera and a multi-functional
sensor detect that someone enters.
The lighting is turned off when the camera and the multi-functional sensor fail to detect
any person in the aisle within 10 minutes.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
129

Hide quick links: