Philips Bodine ELI Series Installation And Operating Instructions page 3

Advertisement

UnSwHot SwHot COM GND OutHot OutCom
ENCLOSURE
GROUNDING
CAUTION:
• Ensure input and output primary wiring connections are made to the proper terminals. Damage to product may
occur if miss wired.
• Ensure load voltage requirements match the output ratings of this product or damage to the load devices may occur.
STEP #3
WIRING THE EMERGENCY LIGHTING INVERTER'S DIMMING CONNECTIONS (OPTIONAL)
The ELI-S-100 features an industry-standard 0-10 VDC dimming voltage output which allows Emergency operation of one
or more luminaires that consume a total of more than 100 Watts when operating in the Normal mode, (operating from the
AC mains). These luminaires must have AC Drivers (or Ballasts) that are compatible with industry standard 0-10 VDC
dimming operation. The emergency mode output dimming voltage is selectable in 5 steps to provide nominally 20%, 40%,
60%, 80% and 100% light output. Existing area dimming controls can be wired through the ELI-S-100 dimming relay to
allow for normal dimming by occupants of the area during Normal mode operation. Refer to Illustration 3 below to wire
the dimming output voltage to the load and the input connections from a dimming control device, if utilized. See
Illustration 1 for the location of the dimming connector J2 on the product. This dimming voltage level is set by the
installer by operating the switches S701 and S702, which are located at the lower center section of the circuit board
(see Illustration 1). See Step 4 for switch settings.
J2
STEP #4
SETTING THE OUTPUT DIMMING LEVEL (OPTIONAL)
Upon loss of normal AC power, the Emergency Lighting Inverter's internal 0-10 VDC circuit will output a dimming voltage
to the luminaires. PCB Switches S701 and S702 are used to set the 0-10 VDC dimming level. See Illustration 4 which
details the switch positions for the desired level of dimming. Refer to Illustration 1 for the switch locations on the
product. It may be necessary to measure the output power of the Emergency Lighting Inverter, in the emergency run
mode, to ensure the product's maximum output ratings are not exceeded. It is suggested the installer start with the
maximum dim level (20%), increasing the dim level ONLY if the maximum output ratings are not exceeded. See unit label
for output ratings.
CAUTION:
The installer must ensure the total output power of the Emergency Lighting Inverter does not exceed 100 Watts, in
emergency mode.
20%
40%
60%
ILLUSTRATION 2
PRIMARY WIRING CONNECTIONS
J3
COM OUTPUT
HOT OUTPUT
GROUND
COMMON
SWITCHED HOT
UNSWITCHED HOT
ILLUSTRATION 3
DIMMING CONNECTIONS
DIM- OUT
DIM+ OUT
DIM- IN
DIM+ IN
0-10 VDC + IN
INPUT FROM 0-10 VDC DIMMER (OPTIONAL)
0-10 VDC - IN
0-10 VDC + OUT
OUTPUT TO AC BALLAST 0-10 VDC INTERFACE
0-10 VDC - OUT
ILLUSTRATION 4
DIMMING LEVEL SWITCH SETTINGS
80%
100%
3
OUTPUT CONNECTIONS
AC POWER SOURCE INPUT