5.5 GROUPED ELEMENTS
The COMMON DISTANCE SETTINGS described earlier must be properly chosen for correct operation of the phase dis-
tance elements.
Ensure that the
VOLTAGE BANK
WARNING
PHS DIST Z2 DIRECTION:
Zone2 is reversible. The forward direction by the
that angle.
PHS DIST Z2 SHAPE:
This setting selects the shape of the phase distance function between the mho and quad characteristics. The two charac-
teristics and their possible variations are shown in the following figures.
5
5-62
PHASE VT SECONDARY VOLTAGE
menu) is set correctly to prevent improper operation of associated memory action.
PHS DIST Z2 RCA
X
DIR COMP LIMIT
Figure 5–22: MHO DISTANCE CHARACTERISTIC
X
COMP LIMIT
DIR COMP LIMIT
LFT BLD RCA
-LFT BLD
Figure 5–23: QUAD DISTANCE CHARACTERISTIC
L90 Line Differential Relay
ÖØ
setting (see the
SETTINGS
setting, whereas the reverse direction is shifted 180° from
COMP LIMIT
DIR COMP LIMIT
DIR RCA
RCA
R
837720A1.CDR
COMP LIMIT
DIR COMP LIMIT
DIR RCA
RCA
RGT BLD RCA
RGT BLD
5 SETTINGS
Ö
SYSTEM SETUP
AC INPUTS
R
837721A1.CDR
GE Power Management
ÖØ