ABB UniGear Series Engineering Manual page 49

Table of Contents

Advertisement

E NG INEE R ING
The data set defines what protection relay data is used in GOOSE service and sent to local
Ethernet subnetwork in a GOOSE message. The GOOSE control block links the data set and
its attributes to actual data.
GOOSE Control Block Attributes
– APPID – unique GoID in network
Reserved value is ranging from
– MAC address
Unique Multicast address per GoCB is recommended
The allowed multicast address ranges from
– GOOSE Control block name
– Data set definition
– VLAN ID
The default value is 0x000; it should be configured to > 0
Recommended values (as per IEC 61850-90-4) are ranging from
(1 511)
– VLAN priority
The default value is 4 as per IEC 61850-8-1 (value range 0 ...7)
– T min (ms)
Maximum response time to data change
– T max (ms)
Heartbeat cycle time in (the default value is 10 000 ms)
– ConfRev
Its value increases when referenced data set becomes modified
1V LG 5 000 07 E
0x0000
0x3FFF
to
(Ed.1)
01-0C-CD-01-00-00
S TAT IO N BU S (G O OS E)
01-0C-CD-01-01-FF
to
0x3E8 (1 000)
0x5E7
to
37