Opc Integration Configuration - Siemens DMS8000 Applications And Planning Manual

Mp4.10 for mm8000 management station; mk8000 opc server; mt8001 management terminal; nk8000 networks
Hide thumbs Also See for DMS8000:
Table of Contents

Advertisement

Automation level configurations
3.3.9

OPC integration configuration

See MM8000 MP4.10 Release Notes (STEP #A6V10062455)
36
Building Technologies
Fire Safety & Security Products
Fig. 17
OPC integration configuration
System architecture
This configuration allows for the integration of 3
OPC server.
OPC connectivity for subsystems can be provided in "light" or "full" mode.
- Light: Free, but requires more engineering (e.g. SIMATIC S7)
See the OPC Connectivity Guide (STEP #A6V10065253)
- Full: Requires development of a Composer subsystem tool (e.g. RCO
R-Card M5)
Communication / connection
rd
3
party subsystems are connected via Ethernet to the OPC server, which may run on
the MM8000 Management Station or on a networked PC. MM8000 connects to the
OPC server for all of the communication to/from the subsystems.
Subsystems that can be connected in this way
Type
Name
I/O System
SIMATIC S7
Access Control
RCO R-Card M5
Additional components required for the various management station types
Type
MM8000
Limits and restrictions
Type
Version
MM8000
MP4.10
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Version
Additional
components
rd
3
party OPC server
Restrictions
8 OPC connections
10,000 OPC tags (in total)
rd
party subsystems equipped with an
Supported by
MM8000
MK8000
MP4.10
MP4.10
X
X
Name
Version
Please contact customer sup-
port for more connections, tags.
MT8001
MP3.15
06.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents