Limitation:
Too short of an Accel time can result in Torque limit warning (W12) and/or DC over voltage warning (W7). Ramping is stopped when the frequency converter has
reached Torque limit motor mode (par. 4-16).
Too short of a Decel time can result in Torque limit warning (W12) and/or DC over voltage warning (W7). Ramping is stopped when the frequency converter reaches
the Torque limit generator mode (par. 4-17) and/or the internal DC over voltage limit.
3-40 Accel/Decel 1 Type
Option:
*
Linear
[0]
[2]
S-ramp
4
3-41 Accel Time 1
Range:
*
3.00 s
[0.05 - 3600.00 s ]
3-42 Decel Time 1
Range:
*
3.00
[0.05 - 3600.00 s]
4.4.5. 3-5* Accel/Decel 2
See par. 3-4* for a description of ramp types.
NB!
Accel/Decel 2- alternative ramp times:
Changing from Accel/Decel 1 to Accel/Decel 2 is done via the digital input. See par. 5-1*, selection [34].
3-50 Accel/Decel 2 Type
Option:
Linear
*
[0]
[2]
S-ramp
3-51 Accel Time 2
Range:
*
3.00 s
[0.05 - 3600.00 s]
3-52 Decel Time 2
Range:
3.00 s [0.05 - 3600.00 s]
4.4.6. 3-8* OtherAccel/Decel Ramps
This section contains parameters for Jog and Quick Stop Ramps.
With a Jog Ramp you can both ramp up and down whereas you can only ramp down with the Quick Stop Ramp.
28
Function:
Constant acceleration/deceleration.
Smooth jerk compensated acceleration/deceleration.
Function:
Enter accel time from 0 Hz to rated motor frequency (f
Choose a accel time ensuring that torque limit is not exceeded, see par. 4-16.
Function:
Enter decel time from rated motor frequency (f
Choose a decel time that does not cause over-voltage in due to regenerative operation of motor. Furthermore, regen-
erative torque must not exceed limit set in par. 4-17.
Function:
Constant acceleration/deceleration.
Smooth jerk compensated acceleration/deceleration.
Function:
Enter accel time from 0 Hz to rated motor frequency (f
Choose a accel time ensuring that torque limit is not exceeded, see par. 4-16.
Function:
Enter decel time from rated motor frequency (f
Choose a decel time that does not cause over-voltage in due to regenerative operation of motor. Furthermore, regen-
erative torque must not exceed limit set in par. 4-17.
AF-60 LP™ Micro Drive Programming Guide
) set in par. 1-23.
M,N
) in par. 1-23 to 0 Hz.
M,N
) set in par. 1-23.
M,N
) in par. 1-23 to 0 Hz.
M,N