Operation; Configuring And Wiring Analog Inputs; Input Wiring For Connecting Thermocouples To Channels 0 Through - Siemens SIMATIC S5 Manual

Ip 244 temperature controller with function block fb 162
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

3

Operation

3.1 Configuring and Wiring Analog Inputs

The analog signals are connected via the X3 front connector. There are 16 differential inputs on
a module.
The sensitivity of the analog inputs is selected by configuring plug-in jumpers:
0 ... 51.2 mV for thermal e.m.f. (selection upon delivery)
0 ... 512 mV for general input voltage values
The selection is valid for all analog inputs.
Unused analog inputs should be shorted to avoid interference.
3.1.1 Input Wiring for Connecting Thermocouples
to Channels 0 through 12 (0 ... 51,2 mV = 2048 units resolution)
The voltage difference U
CM
mocouples may be used as long as the maximum voltage difference is not exceeded (grounding
thermocouples is recommended, though).
Fig. 3.1.1/1 Input wiring of thermocouple
IP244B
C79000–B8576–C865–01
may not exceed 25 VAC (120 VAC test voltage). Ungrounded ther-
Operation
3–19