Chapter 3 Application System Architecture

Figure 2: RX3i Genius Dual Bus Interfaced to RX3i via Genius Gateway Modules (GCG001)

A typical system consists of at least two RX3i racks, with the following components in each rack:
One or more power supplies
One PLC CPU module (IC695CPE330 or equivalent)
Two RMX reflective memory exchange modules (for CPU synchronization)
Fiber optic cables for the RMX modules
One or more PROFINET Controller modules
Additionally, the system will require the following items to interface with each dual Genius I/O network:
Four Genius Communications Gateway modules (two associated with the Primary PLC interface and
two with the Secondary PLC interface).
Cat5 or 6 Ethernet Cables to interconnect the Gateways with the PROFINET Controllers
Optional - interposing Ethernet switches that may be installed to provide additional MRP ring
functionality
Optional – Connectors that provide Hand Held Monitor attachment points for each of the Genius
busses. (GE catalog number 44A736310-001-R001. Refer to Genius Hand-Held Monitor User's Guide,
GFK-0121, page 2-9 for further information).
If a CPE400 is used, the RMX links are replaced with LAN3 links.
1
GFK-2928
December 2017
1