Group
97 USER MOTOR PAR
User adjustment of motor model values estimated during ID run. The values can be
entered in either "per unit" or SI.
97
97 USER MOTOR PAR
97.01 USE GIVEN PARAMS
Activates the motor model parameters 97.02...97.14.
The value is automatically set to zero when ID run is selected by parameter
values of parameters
during the ID run.
Note: This parameter cannot be changed while the drive is running.
(0) NO
(1) USE GIVEN
97.02 RS USER
Defines the stator resistance R
0...0.5 p.u. (per unit)
97.03 RR USER
Defines the rotor resistance R
Note: This parameter is valid only for asynchronous motors.
0...0.5 p.u. (per unit)
97.04 LM USER
Defines the main inductance L
Note: This parameter is valid only for asynchronous motors.
0...10 p.u. (per unit)
97.05 SIGMAL USER
Defines the leakage inductance
Note: This parameter is valid only for asynchronous motors.
0...1 p.u. (per unit)
97.06 LD USER
Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet motors.
0...10 p.u. (per unit)
FW block: None
97.02...97.14
are updated according to the motor characteristics identified
Inactive.
The values of parameters
FW block: None
of the motor model.
S
Stator resistance.
FW block: None
of the motor model.
R
Rotor resistance.
FW block: None
of the motor model.
M
Main inductance.
FW block: None
σ
L
.
S
Leakage inductance.
FW block: None
Direct axis (synchronous) inductance.
99.13 IDRUN
97.02...97.14
are used in the motor model.
Parameters and firmware blocks