Sicam Ak - Sicam Tm Pe, Optical, Red. Bse + Red. Ax-Pe-Bus - Siemens SICAM AK Manual

Rtus. redundancy,
Table of Contents

Advertisement

Redundancy via SCA-RS
1.2.1.4

SICAM AK - SICAM TM PE, Optical, Red. BSE + Red. Ax-PE-Bus

Base unit SICAM AK to peripheral elements SICAM TM, optically connected, redundant basic
system elements and redundant Ax-PE-Bus.
base unit
SICAM AK
RY
RY
RY
RY
RY
RY
RY
ER
ER
ER
ER
ER
ER
ER
ESD
EARTH
FACILITY
To one basic system element
CP-2017/PCCX25 one bus line with max.
16 peripheral elements can be connected
The slots for the redundant BSE-pairs are
predefined, in fact: 1+2, 4+5, 7+8, (10+11,
13+14 only in 17 slots mounting rack)
Depending on the slots of the basic system
elements the socket connectors for the
electrical Ax peripheral bus have to be
selected (for example: slots C1 and C2 
socket connectors AXPE-C1 and AXPE-C2)
In configurations with optical remote
SICAM TM PEs 1000 µm-fibre cables cannot
be used!
Redundant BSEs have to have identical
configuration and identical functionality
Each bus interface module CM-0842 has to be
supplied separately (18 VDC...78 VDC)
30
1
SICAM
RY
RY
RY
RY
RY
RY
RY
RY
RY
RY
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
PS-5620
CP-2017
CP-2014
bus interface modules
CM-0842
2
Unrestricted
Ax peripheral bus (electrical)
16 Mbps
patch-cable, length up to 3 m
S1
ON
OFF
2
Ax peripheral bus (optical)
16 Mbps
FO, length up to 200 m
PS-663x
PE-6412
I/O modules (max. 8)
1 peripheral element
Attention: Break of an FO-connection leads
to a failure of the peripheral elements
PE-6412 until the redundant basic system
element duly assumes the function
During this time connection to the peripheral
elements PE-6412 does not exist
Configuration switch CM-0842
1 ....... F1/F2 ....... ON ...... 16 MBit
2 ....... LINE2 ....... OFF ..... PE(O)
3 ....... AS2 .......... OFF ..... 0
4 ....... AS1 .......... OFF ..... 0
5 ....... AS0 .......... OFF ..... 0
6 ....... RED ......... OFF ..... CM-0842
7 ....... LAD .......... OFF ..... inactive
8 ....... LINE1 ....... ON ...... PE
SICAM RTUs, SICAM AK Redundancy
Edition 10.2016, DC2-026-2.07
S1
ON
OFF
peripheral elements
SICAM TM
(max. 16 PE)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents