PID Controller FCM
BAD INPUTS ACCEPTED Field
This field specifies whether an input with BAD data quality is treated as if the data
quality is GOOD. Valid entries are:
ACTION ON BAD INPUT Field
This field specifies the action to take if the controller input signal goes to BAD data
quality. Valid entries are:
ACTION ON BAD SETPT Field
This field specifies the action to take if the setpoint signal goes to a BAD data
quality. Valid entries are:
SETPOINT RETURN MODE Field
This field specifies the setpoint mode to enter when the mode returns from Track.
Valid entries are:
236
NO
do not accept bad inputs
YES
accept bad inputs
FCM OFF controller FCM is turned off
MAN OUT controller FCM goes to the Manual output mode
NONE
FCM continues processing according to its configuration
NONE
no special action is taken
MAN OUT output mode is switched to Manual
LOC SPT
setpoint mode goes to Local
FCM OFF FCM is turned off
PREVIOUS go to the mode active before the setpoint went to Track
LOCAL
go to the Local mode
REMOTE
go to the Remote mode
Appendix A Runtime Templates
3BUR002418-600 A