  • Page 1 Original instructions Vital 2 and Vital 3 Operating instruction Vital2&3_Manual_v1D www.jokabsafety.com...
  • Page 2 General Vital is based on a single-channel safety concept where several safety components (e.g. sensors) can be connected in series and supervised with only one safety module. A dynamic signal is sent from Vital through all connected components, and then back to Vital which evaluates the received signal.
  • Page 3: Output Groups

    Spot “Spot” is a safety light beam which is available in two versions, Spot 10 for distances up to 10 m and Spot 35 for distances up to 35 m. The light beams can be mounted at different heights and be angled around a machine using special mirrors and brackets.
  • Page 4: Time Delay

    Time delay Output group 2 can be off-delayed by connecting the inputs 0.5s and 1.0s to +24V. The system is binary so connection of one of these inputs adds the corresponding time. Connecting 0.5s = 0.5 sec. delay Connecting 1.0s = 1.0 sec. delay Connecting both 0.5s and 1.0s = 1.5 sec.
  • Page 5 Mode M1 - Separate function Input function 1 controls output group 1, and input function 2 controls output group 2. Input function 1 Input function 2 Safety Safety sensors sensors Test Test Reset 1 Reset 2 Input & reset logic Input &...
  • Page 6 Mode M2 - Input 1 master control function Input function 1 stops all outputs, and input function 2 stops output group 2. Input function 1 Input function 2 Safety Safety sensors sensors Test Test Reset 1 Reset 2 Input & reset logic Input &...
  • Page 7 Mode M3 - Parallel function Input function 1 and Input function 2 works in parallel and controls all outputs. Reset/Auto reset 1 resets both input functions (Reset/Auto reset 2 is not used). Input function 1 Input function 1 Input function 2 Input function 2 Safety Safety...
  • Page 8: Connection Example

    Connection example This example shows a Vital 2 in Mode M1 with 2 Eden sensors, a reset button and a Smile Tina emergency stop button. +24V Eden Sensors Smile Tina Reset Vital 2 0.5s 1.0s -24V -24V +24V +24V +24V The Eden sensors are in this example regarded to be interlocking sensors on a guard that can be passed and has therefore a reset function.
  • Page 9: Technical Data

    Technical data Supply Nominal voltage 24 VDC Tolerance +/-15% Max interruption 20 ms Recommended external fuse Safety outputs Solid state: Q2, Q12 Output voltage (nominal): - 24V Output voltage by load: > 22V at 800 mA / 24V supply voltage 23.3 V at 150 mA / 24V supply voltage Max.
  • Page 10 Status messages and error codes Status messages Description Power up Run mode (1 = Mode M1, 2 = Mode M2, 3 = Mode M3) User faults Fault and possible reason. Reset action Er10* T1 or T11 short circuited to foreign voltage. Automatically reset Er12* Short circuit between two dynamic inputs...
  • Page 11: Ec Declaration Of Conformity

    EC declaration of conformity JOKAB SAFETY AB declare that the safety components of JOKAB SAFETY Boplatsgatan 3 manufacture, with type designations and safety functions as SE-213 76 Malmö listed below, are in conformity with the Directives Sweden 2006/42/EC 2004/108/EC 2006/95/EC Göran Svensson Person authorised to compile the technical file...