Terminal modules TPS (witch), 3-wire initiators with LED, incl. switch in the signal path
6ES7924-0CH20-0Bx0
Clearances and creepage distances
Dimensions (W x H x D) in mm
For 3-wire initiators with disconnector
6ES7924-0CH20-0Bx0
Table 6-8
Terminal modules TP2, 2 A modules without LED
6ES7924-0BB20-0Ax0
Type of supply voltage
Operating voltage
Max. permissible continuous current per signal
Connection to SIMATIC fitted for
Operating temperature
Mounting position
Clearances and creepage distances
Dimensions (W x H x D) in mm
For 2 A modules 6ES7924-0BB20-0Ax0
Table 6-9
Terminal module TPRi 230 V with relay for inputs
6ES7924-0BE20-0Bx0
Energizing side
Operating voltage for coil
Input circuit
Contact side
Number of relay outputs
Contact design
Switching capacity (resistive load)
Switching frequency
Service life
Mechanical
System cabling for S7-300
Manual, 09/2018, 70327045899
Technical specifications for terminal module TP2 without LED
Technical specifications for terminal module TPRi 230 V
6.7 Technical specifications for terminal modules
IEC 60664-1, IEC61131-2,
CSA C22.2 No 142 UL 508, VDE 0160,
Overvoltage category II,
pollution degree 2
Approx. 57 x 76 x 60
DC
max. 50 V
2 A
16-pin IDC connector with fitted strain relief
0 to + 60° C
Any
IEC 60664-1, IEC61131-2,
CSA C22.2 No 142 UL 508, VDE 0160,
Overvoltage category II,
pollution degree 2
Approx. 57 x 76 x 60
230 V AC / from 207 – 264 V AC
Suppressor diode
8 NO contacts
Single contact, 1 NO contact
max. 50 mA / 24 V DC
max. 50 mA / 48 V DC
max. 50 mA / 60 V DC
Recommended minimum load ≥ 5mA
500 cycles/minute
10 x 10
switching cycles
6
Technical specifications