Reading out/saving service data

Introduction
In addition to the contents of the diagnostics buffer, the service data contain numerous
additional data points about the internal status of the CPU. If a problem with the CPU should
occur, that cannot otherwise be resolved, please send the service data to our Service &
Support. The service data allow Service & Support to analyze problems that have occurred
rapidly.
Requirements
Service data can be read out via the Web server. For this reason the Web server has to be
activated.
Procedure
1. Open a web browser that is suitable for communication with the CPU.
2. Enter the following address in the address bar of the web browser:
3. The service data page will appear on your screen, with a button for saving the service
4. Save the service data locally on your PC/programming device, by clicking "Save
Result: The data are saved in a .dmp file with the following naming convention: "<MLFB>
<serial number> <time stamp>.dmp". The file name can be changed.
S7-1500 Automation System
System Manual, 01/2013, A5E03461182-01
https://<CPU IP address>/save_service_data.html,
e.g., https://172.23.15.3/save_service_data.html
data.
Figure 10-1
Reading out service data via the web server
ServiceData".
Test functions and fault resolution
10.2 Reading out/saving service data
133