 Connecting flange
Refer to size in the figure attached to the main unit.
<MMD-AP048 type>
<Air supply port connecting flange>
1.8"
(45)
25.6" (650) (2.6" × 10 (65 × 16))
2.6" (65)
42.6" (1083)
0.4" (9)
0.7" (19)
<Air intake port connecting flange>
2.2"
(55)
20.5" (520) (2.6" × 8 (65 × 8))
2.6" (65)
23.0" (583)
0.4" (9)
0.7" (19)
REQUIREMENT
If the air conditioner unit and the canvas joint are connected with the rivets, the fan and the refrigerating cycle cannot
be checked.
Be sure to use the flange as shown in the above and tighten it by the bolts.
(Fixing bolts 0.2" x 0.5" (6 x 12 mm), locally procured)
13-EN
<MMD-AP072 type, AP096 type>
<Air supply port connecting flange>
1.8"
(45)
40.9" (1040) (2.6" × 16 (65 × 16))
2.6" (65)
42.6" (1083)
0.4" (9)
0.7" (19)
<Air intake port connecting flange>
1.8"
(45)
40.9" (1040) (2.6" × 16 (65 × 16))
2.6" (65)
42.6" (1083)
0.4" (9)
0.7" (19)
– 7 –
<Example of construction>
Air supply duct *1
Air supply flange
Heat insulator *1
Canvas duct *1
Product main unit
1
Air intake duct
• Connect the air intake duct (Locally procured) to the inlet flange.
Wrap aluminum tape around connecting part between the air intake port flange and duct, or provide sealer
so that air does not leak.
• For the outside air intake port, attach a hood so that outside air is sucked from lower side.
And attach wire netting, etc. to the air intake of the hood.
• Set the air intake duct at descending inclination so that water can be drained even if rainwater enters in.
• Wrap the outside of the intake duct with heat insulator because it intakes cold air while heating.
2
Air supply duct
Connect the air supply duct (Locally procured) to the Air supply flange.
Wrap aluminum tape around connecting part of the air supply port flange and duct or apply packing so that air
does not leak.
High-efficiency filter *1
Long life prefilter *1
Air intake flange
*1
*1
Heat insulator *1
Air intake duct
*1
Descending
inclination
Filter chamber *1
Canvas duct *1
Check port
(23.6" × 23.6" in
(600 × 600 mm))
*1
Wall
*1: Locally procured
Hood
(with wire netting)
*1
14-EN