Cooling Fans; Fan Speed Control - GE AF-650 GP Operating Instructions Manual

High power unit sizes 6x
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

3.3.5 Cooling Fans

All frequency converters in this size range are equipped with cooling fans to provide airflow along the heatsinks and within the enclosures. All fans are powered
by mains voltage which is stepped down by autotransformers and regulated to 200 or 230 VAC by circuitry provided on the power cards. On/off and high/low
speed control of the fans is provided to reduce overall acoustical noise and extend the life of the fans.
Fans are activated by the following causes:
60% of nominal current exceeded
Specific heatsink temperature exceeded (power size dependent)
Specific power card ambient temperature exceeded
Specific control card ambient temperature exceeded
DC hold active
DC brake active
Pre-magnetization of the motor
Automatic motor adaptation in progress
Regardless of the heatsink temperature, the fans are started shortly after main input power is applied to the frequency converter.
Once fans are started, they will run for a minimum of 10 minutes.

3.3.6 Fan Speed Control

The cooling fans are controlled with sensor feedback which regulates fan operation and speed control as described below.
IGBT thermal sensor measured temperature. The fan can be off, low speed, or high speed based on this temperature.
IGBT Thermal Sensor
Fan turn ON low speed
Fan low speed to high speed
Fan high speed to low speed
Fan turn OFF from low speed
Table 3.1: IGBT Thermal Sensor
Power card ambient temperature sensor measured temperature. The fan can be off or high speed based on this temperature.
Power Card Ambient
Fan turn ON to high speed
Fan turn OFF from high speed
Fan turn ON to high speed
Table 3.2: Power Card Ambient Temperature Sensor
Control card thermal sensor measured temperature. The fan can be off or low speed based on this temperature.
Control Card Ambient
Fan turn ON to low speed
Fan turn OFF from low speed
Table 3.3: Control Card Thermal Sensor
Output current value. If the output current is greater than 60% of rated current, the fan will turn on low speed.
Temperature
45° C
50° C
40° C
30° C
Temperature
45° C
40° C
<10° C
Temperature
55° C
45° C
High Power Service Manual for Unit Sizes 6x
3
43