Siemens Desigo RXB Technical Manual page 335

Technical manual
Table of Contents

Advertisement

Power demand
ETS3 Professional
ACS Service
HandyTool
Siemens
Building Technologies
If an electric reheater is used, the controller makes the present power demand
available on the bus.
In order for this to happen, the capacity of the heater battery must be written to the
controller via the tool.
Select Sequences, Power consumption el heater :
Select Sequences, Power consumption :
Parameter
Short name
*057
Power consumption el heater
RXB (KNX) application library
Control sequences
FNC Description of functions for FC-10, FC-11, FC-12
Basic setting
0 W
CM110385en_05
28 Feb 2009
99/166

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents