Displays and Mode Selector
Controlling the Operating Status
There are different ways of controlling the mode of the CP 443-5 Basic, as follows:
S Mode Selector
S NCM S7 for PROFIBUS configuration software
S SIMATIC Manager in STEP 7
To control the mode from STEP 7 / NCM S7 for PROFIBUS, the mode selector
must be set to RUN.
Mode Selector
With the mode selector, you can set the following operating statuses:
S Switch from STOP to RUN:
The CP reads the configuration data into the work memory and then changes to
the RUN mode.
S Switch from RUN to STOP:
The CP changes to STOP with the following results:
– Established connections (FDL, FMS connections, configured, and
unconfigured S7 connections) are terminated
In the STOP mode
– Configuration and diagnostics are possible
– The time of day is distributed
Note
Refer to the explanations in the manual /2/ on the topic of loading the database on
the CP.