Parameters/address space

4.1

Parameter

DI 32x24VDC HF parameters
When you assign the module parameters in STEP 7, you use various parameters to specify
the module properties. The parameters that can be set depend on whether you use the
module in standard mode or in counter mode. You will find the parameters in section
Parameters DI mode (Page 16) or section Parameters of the Counting mode (Page 18). The
effective range of the configurable parameters depends on the type of configuration. The
following configurations are possible:
● Central operation with a S7-1500 CPU
● Distributed operation on PROFINET IO in an ET 200MP system
● Distributed operation on PROFIBUS DP in an ET 200MP system
For parameter reassignment in the user program, the parameters are transferred to the
module with the WRREC instruction (parameter reassignment in RUN) using data records;
see section Parameter assignment and structure of the parameter data records (Page 45).
4.1.1

Parameters DI mode

Parameters of the DI 32x24VDC HF in the DI mode
In the following table, you will find the parameters in the "DI mode". These parameters apply
to channels 0 to 31.
Table 4- 1
Settable parameters and their defaults in the DI mode
Parameter
Diagnostics
No
supply voltage L+
Wire break
Input delay
16
Range of val-
Default setting
ues
Yes/No
No
Yes/No
No
0.05 ms,
3.2 ms;
0.1 ms, 0.4 ms,
for isochronous
1.6 ms, 3.2 ms,
mode 0.05 ms
12.8 ms, 20 ms
(cannot be
changed)
Parameter
Range of effectiveness with configura-
reassignment
tion software, e.g. STEP 7
in RUN
Integrated in the
hardware catalog as
of STEP 7, V13 SP1
or GSD file
PROFINET IO
Yes
Channel*
Yes
Channel
Yes
Channel
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
4
GSD file
PROFIBUS DP
Channel group**
Channel group**
Channel group**
Manual, 09/2016, A5E03485935-AF