GENERAL DESCRIPTION
CONTACTOR RATINGS
Rated Voltage
Rated Current
Interrupting Capacity
Permissible Switching Frequency
Mechanical Life
Electrical Life
Closing Time
Opening Time *
Arcing Time
Pick-Up Voltage AC or DC
Drop-Out Voltage AC or DC
Rated Control Voltage AC
Rated Control Voltage DC
Coil Circuit Inrush
Coil Circuit Holding
Auxiliary Contact Arrangement
Auxiliary Contact Rating
* - DC switching, opening terminals 3 & 4.
Permissible Switching Frequency
Mechanical Life
Tripping Voltage
Tripping Current
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
HCV-5HA
7000A RMS Symmetrical @5000V Max.
4500A RMS Symmetrical @7200V Max.
85% Rated (Hot) - 70% Rated (Cold)
50% Rated (Hot) - 40% Rated (cold)
115/120 or 230/240 V 50/60 Hz
670 VA AC (700 W DC)
10 A, 600 V (NEMA Class A600)
HCV-5HAL (Latched Type Only)
7200 Volts
400 Amps
1200/Hour
2,500,000 Operations
250,000 Operations
75-100 ms
20-30 ms
10 ms or less
120/125 or 240/250 V
85 VA AC (85 W DC)
3 N.O. - 3 N.C.
300/Hour
250,000 Operations
40-60% Rating DC
4.8 A DC Max