Download Print this page

Bosch B426 Installation Manual page 2

Conettix ethernet communication module

Advertisement

5 | LED descriptions
The B426 module includes the following on-board LEDs to assist
with troubleshooting issues (refer to Figure 1.1 for the location of the
LEDs):
– Heartbeat (system status). Refer to Table 5.1.
– Data Bus communication. Refer to Table 5.2
– Ethernet communication. Refer to Table 5.3.
Flash pattern Function
Flashes once
Normal state: Indicates normal operation state.
every 1 sec
3 quick flashes
Communication error state: Indicates (the
every 1 sec
module is in a "no communication state")
resulting in an SDI2 communication error.
On Steady
LED trouble state: Module is not powered
(for OFF Steady only), or some other
trouble condition prohibits the module from
Off
controlling the heartbeat LED.
Table 4.1: Heartbeat LED descriptions
Flash pattern Function
RX (Receive)
Occurs when the control panel bus receives a
flashes
message.
TX (Transmit)
Occurs when the control panel bus sends a
flashes
message.
Table 4.1: Data bus LEDs descriptions
LINK (yellow)
100mb (green)
Function
flash pattern
flash pattern
Off
Off
No Ethernet link
On Steady
Off
10 BASE-T link
Flash
Off
10 BASE-T activity
On Steady
On Steady
100 BASE-T link
Flash
On Steady
100 BASE-T activity
Table 4.1: Ethernet LINK and 100mb LEDs descriptions
6 | Show the firmware version
To show the firmware version using an LED flash pattern:
– If the optional tamper switch is installed:
With the enclosure door open, activate the tamper switch (push and
release the switch).
– If the optional tamper switch is NOT installed: Momentarily short
the tamper pins.
Refer to Figure 6.1 for an example of flash patterns.
Figure 6.1: Firmware LED flash patterns
When the tamper switch is activated (closed to open), the heartbeat
LED stays OFF for 3 sec before indicating the firmware version.
The LED pulses the major, minor, and micro digits of the firmware
version, with a 1 sec pause after each digit.
Flashing patterns do not start until the tamper is open (short is
removed). In the following is an example, the version 1.4.3 shows as
LED flashes:
[3 sec pause] *___****___*** [3 sec pause, then normal operation].
7 | Certifications
Region
Certification
US
UL 365 – Police Station Connected Burglar Alarm Units and Systems
UL 609 – Local Burglar Alarm Units and Systems
UL 864 – Control Units and Accessories for Fire Alarm Systems
(Including NFPA 72)
UL 985 – Household Fire Warning System Units
UL 1023 – Household Burglar Alarm System Units
UL 1076 – Proprietary Burglar Alarm Units and Systems
UL 1610 – Central Station Burglar Alarm Units
FCC Part 15 Class B, NIST FIPS-197 AES Certification
(IP Communications)
Canada
CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control
Units
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and
Systems
ICES-003 - Digital Apparatus
8 | Specifications
Dimensions
59.5 mm x 108 mm x 16 mm (2.19 in x 4.25 in x 0.629 in)
Voltage (operating)
12 VDC nominal
Current (maximum)
100 mA max
Connectors
LAN/WAN: RJ-45 modular port (Ethernet)
Ethernet cable
Category 5 or better unshielded twisted pair, 100 m (328 ft) max length
Interface
IEEE 802.3
Data bus wire size
1.02 mm to 0.65 mm (18 AWG to 22 AWG)
Data bus wire length
Maximum distance - Wire size:
150 m (500 ft) - 0.65 mm (22 AWG)
300 m (1000 ft) - 1.02 mm (18 AWG)
Web browser
Microsoft Internet Explorer 6 or higher; Mozilla Firefox 3 or higher
Compatibility
D9412, D7412, D7212, D9112
G Series Version 6.3 or higher
GV2 Series
GV3 Series
GV4 Series
B5512/B4512/B3512
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at
http://www.boschsecurity.com/datecodes/.
Applicable control panels
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
GV4 Series, GV3 Series, GV2 Series, FPD-7024
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series, G Series,
DS7200, DS7400, Easy Series V3+, AMAX 2000
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
B5512/B4512, GV4 Series, GV3 Series, GV2 Series
Conettix Ethernet Communication
Module
B426
en Installation Guide (UL)
For complete installation, confi guration, and testing instructions,
refer to the Conettix Ethernet Communication Module (B426)
Installation and Operation Guide provided on the supplied
CD-ROM.
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA
www.boschsecurity.com
© 2013 Bosch Security Systems, Inc.
F.01U.281.209 | 02 | 2013.08

Advertisement