Siemens Sinamics S120 Manual page 753

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

The shield is connected as shown below.
Figure 12-33 Shield connection using a motor connector, crimped version, as example
Shield support on a toothed rail
The toothed rail should be mounted at a distance of ≤ 150 mm below the drive line-up to
ensure a good contact. Wherever possible, the brake cores must be kept physically separate
from U/V/W connections.
Note
Measures must be taken on site to relieve strain on the cables.
The maximum permissible tensile load in the insertion direction is 100 N.
With these versions, the shield for the brake connection conductors must be routed together
with the cable shield.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Protective braided shield
Steel hose clamp
Cabinet design and EMC Booksize
12.8 Connection systems
753

Advertisement

Table of Contents
loading

Table of Contents