8.5.4 Chart Rotation Troubleshooting
Procedure
Table 8-8 explains how to troubleshoot a chart rotation problem.
Step
Check the chart installation.
1
Check the configured chart speed value
2
and change it, if required.
Run the step test.
3
Check the motor cable plug connection at
4
connector P3 on the printed circuit
assembly for pen 1.
5
Replace the chart motor.
Replace the printed circuit board for pen
6
1.
4/00
Table 8-8 Troubleshooting Chart Rotation Failure Symptoms
What to do
DR4300 Circular Chart Recorder Product Manual
Troubleshooting and Pen Alignment
of Recorder with Display
How to do it or
where to find the instructions
Turn the chart until the desired time line on the
chart is aligned with the time index on the chart
plate and pen 1 before closing the locking clip on
the hub. Push down on the lifter to return the
pen(s) to the chart.
CAUTION: Do not try to rotate the hub
Refer to Section 4 – Configuration, Startup, and
Operation of Recorder with Display.
Refer to Section 4 – Configuration, Startup, and
Operation of Recorder with Display (Subsection
4.4.3).
Power down the recorder, then visually examine
the plug and re-seat it.
Refer to the replacement procedure in Section 9
– Replacing Hardware Assemblies.
Refer to the replacement procedure in Section 9
– Replacing Hardware Assemblies.
183