Application Set-up Examples
6 Application Set-up Examples
6.1 Introduction
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
K-03 Regional Settings)
•
Parameters associated with the terminals and
their settings are shown next to the drawings.
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
6.2 Application Examples
Table 6.1 Analog Speed Reference (Voltage)
AF-600 FP Design and Installation Guide
Parameters
Function
Setting
AN-10 Terminal
53 Low Voltage
0.07 V*
AN-11 Terminal
10 V*
53 High Voltage
AN-14 Terminal
0 RPM
53 Low Ref./
Feedb. Value
AN-15 Terminal
1500 RPM
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
DET-768A
AN-12 Terminal
53 Low Current
AN-13 Terminal
53 High Current
AN-14 Terminal
53 Low Ref./
Feedb. Value
AN-15 Terminal
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Table 6.2 Analog Speed Reference (Current)
Figure 6.1
Parameters
Function
Setting
4 mA*
20 mA*
0 RPM
1500 RPM
6-1
6
6