1. Specifications Wall mounted Type Inverter heat pump Model name ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE Power supply 230 V ~ 50 Hz Available voltage range 198—264 V 2.00 2.50 3.40 4.00 Rated Btu/h 6,800 8,500 11,600 13,600 Cooling 0.5—3.0 0.5—3.2 0.9—3.9 0.9—4.4...
2. Dimensions 2-1. Models:ASYG07LMCE, ASYG09LMCE, ASYG12LMCE, and ASYG14LMCE Unit: mm (870) Outline of unit 65 for pipe inlet 65 for pipe inlet - 4 -...
Page 9
¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm Outline of unit 25 or more 52 or more 86 or more 144 or more 1,500 or more - 5 -...
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model:ASYG07LMCE Indoor temperature °CDB °CWB °CDB...
5. Fan performance 5-1. Air velocity distributions ¢ Models:ASYG07LMCE, ASYG09LMCE, and ASYG12LMCE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
Page 14
¢ Model:ASYG14LMCE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
7. Safety devices Model Type of Protection form protection ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE Circuit Current fuse (PCB*) 250 V, 3.15 A protection 105±10°C Activate Thermal Fan motor stop Fan motor protector protection 90±10°C program Reset Fan motor restart *PCB: Printed Circuit Board...
9. External input and output With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details. CNB02 —...
Page 24
When function setting is "Forced stop" mode Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Optional part Part name Model name Exterior External input wire External connect kit UTY-XWZXZ5 Communication kit UTY-XCBXZ2 * For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
9-2. External output With using external output function, operating status of this product can be transmitted to the ex- ternal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. ...
Page 26
¢ Error status output Air conditioner error status signal can be output. Circuit diagram example Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased •...
10. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 10-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting pro- cedure and the content of each function setting, select appropriate functions for your installation environment.
Page 28
NOTES: • The air conditioner custom code is set to prior to shipment. • The remote controller resets to custom code when the batteries on the remote controller are replaced. If you use a custom code other than code , reset the custom code after replacing the batteries.
Page 29
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign Room temperature sensor control for cooling...
Page 30
4) Auto restart Enables or disables automatic restart after a power interruption. Function number Setting value Setting description Factory setting Enable ♦ Disable NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation.
Page 31
9) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable Enable ♦...
10-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the cus- tom code.
12. Optional parts 12-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal Wired remote screen, wide and large keys easy to UTY-RVNYM controller press, user-intuitive arrow key. Wire type: Polar 3-wire Room temperature can be controlled by detecting the temperature Wired remote UTY-RNNYM...
1. Specifications Type Inverter heat pump Model name AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 1,670 1,830 1,940 Airflow rate Heating 1,470 1,600 1,700 Type × Q'ty Propeller fan × 1 Motor output Cooling Sound pressure level *1...
3. Installation space 3-1. Models:AOYG07LMCE, AOYG09LMCE, AOYG12LMCE, and AOYG14LMCE ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: mm When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 40
Multiple outdoor unit installation • When the upper space is open: Unit: mm When there are obstacles at the rear only. When there are obstacles at the front only. 1,000 or more or more When there are obstacles at the front and rear.
Page 41
Outdoor unit installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 1,000 or more 500 or more 200 or more NOTES: •...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models:AOYG07LMCE and AOYG09LMCE NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Model:AOYG12LMCE NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING 0.858 0.868 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 0.960 0.933 0.876 0.885 0.992 0.964 0.937 0.879 0.889 1.000 0.972...
6-3. Model:AOYG14LMCE NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING 0.893 0.909 0.955 0.908 0.924 Indoor unit is higher than outdoor unit *1 0.975 0.959 0.912 0.928 0.992 0.979 0.963 0.916 0.931 1.000 0.987...
9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrat- ed above. - 49 -...
10. Electrical characteristics Model name AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE Voltage 230 ~ Power supply Frequency Max operating current *1 10.5 Starting current Circuit breaker current Power cable Wiring spec. *2 Connection cable *3 Limited wiring length *1: Maximum current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Model Type of Protection form protection AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE 250 V, 20 A Circuit Current fuse (PCB*) protection 250 V, 3.15 A 250 V, 5 A 100±15°C 150±15°C Activate Fan motor stop Fan motor stop Terminal Fan motor protection 120±15°C...