Panasonic EBL128 Operating Instructions Manual page 71

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
FAULT: Site specific data (SSD), FBP x
FBP=1826 / 1828 (Ext. Fire Brigade Panel)
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Wrong type, expansion board x
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583 mounted in the c.i.e.
(EBL128). Also valid for the I/O Matrix board 4582 connected on the
COM loop, i.e. mounted outside the c.i.e.
The board is not the same type as programmed in the SSD. Change
the programming (via EBLWin) or the board.
FAULT: Wrong type of unit zz-aa
Press "" to see the technical address.
FAULT: Wrong type of unit t.addr xxx
zz-aa = Zone-Address. xxx = COM loop address.
The unit is not the same type as programmed in the SSD. Change the
programming (via EBLWin) or the unit.
FAULT: Zone line input zz-aa
Press "" to see the technical address or the expansion board (4580)
number and input number.
FAULT: Zone line input t.addr xxx
FAULT: Zone line input x exp board x
zz-aa = Zone-Address. xxx = COM loop address.
a. Valid for the Multipurpose I/O unit 3361, connected on the COM
loop, monitored zone line input Z: Break on the zone line or wrong /
no end-of-line capacitor / short-circuit (if not programmed for fire
alarm at short-circuit).
b. Valid for the 8 zones exp. board 4580, mounted in the c.i.e.
(EBL128): Break on the zone line, wrong / no end-of-line capacitor /
short-circuit (if not programmed for fire alarm at short-circuit). .
(User programmable fault text; External fault)
A programmable input is used for an external fault to be presented in
EBL128 with a fault message.