Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Time Tag Handling
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Default: Send Long Format
Time Tag
Binary controlled step position information (BSC)
Table 3.4.5.15-1 Configurable BSC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
BSC
Class
Addresses
Command Address
0...16777215
Position Address
0...16777215
Common
Class
Class 1 = 1
Class 2 = 2
Default: Class 1 = 1
Interrogation Group
1...16 (general) or 1...4 (coun-
ters)
Over Write
True = 1
False = 0
Default: False = 0
Priority
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Description
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Description
Common data class according to IEC
61850.
IEC address for command.
IEC address for position.
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.
Interrogation group. 1 - 16 general or 1 -
4 counter interrogation.
Defines whether a new indication value
overwrites an older one in the queue.
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.