Huawei SmartLogger1000 Quick Manual page 11

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

1. Remove an appropriate length of the steel armor and insulation layer from one end of the cable
using a wire stripper.
Unit: mm
2. Remove the terminal block from the SmartLogger COM port.
3. Connect the cable to the SmartLogger terminal block.
(1) Wiring terminal
NOTE
1. Press the white contact plate of the corresponding wiring terminal to flip the metal spring inside
the wiring terminal.
2. Insert the uninsulated part of the core wire into the wiring terminal.
3. Release the white contact plate to fasten the core wire.
4. Insert the terminal block into the SmartLogger COM port.
5. Remove an appropriate length of the steel armor and insulation layer from the other end of the
cable using a wire stripper.
Unit: mm
6. Connect the cable to the protection port on the RS485 signal SPD.
(2) White contact plate
10
NOTICE
Verify that the COM+ port on the
SmartLogger connects to protection port 2 or
8 on the RS485 signal SPD, and that the
COM– port on the SmartLogger connects to
protection port 6 or 12 on the RS485 signal
SPD.