5.4 SYSTEM SETUP
a) MAIN MENU
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
UNIT
The

PHASOR MEASUREMENT UNIT

source, ID and station name, calibration data, triggering, recording, and content for transmission on each of the supported
ports. The reporting ports menus allow specifying the content and rate of reporting on each of the supported ports.
Precise IRIG-B input is vital for correct synchrophasor measurement and reporting. A DC level shift IRIG-B receiver
must be used for the phasor measurement unit to output proper synchrophasor values.
NOTE
The PMU settings are organized in five logical groups as follows.
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
UNIT 1
5
5-80
PHASOR MEASUREMENT UNIT
PHASOR MEASUREMENT
UNIT 1
REPORTING OVER
MESSAGE
NETWORK
menu allows specifying basic parameters of the measurements process such as signal
PHASOR MEASUREMENT UNIT
PMU 1 BASIC
CONFIGURATION
PMU 1
MESSAGE
CALIBRATION
PMU 1
MESSAGE
COMMUNICATION
PMU 1
MESSAGE
TRIGGERING
PMU 1
MESSAGE
RECORDING
L30 Line Current Differential System
5.4.8 PHASOR MEASUREMENT UNIT
See below.
See page 5-95.
PHASOR MEASUREMENT UNIT 1
See page 5-81.
See page 5-82.
See page 5-83.
See page 5-85.
See page 5-92.
5 SETTINGS