Siemens 3VA1 100 A Manual page 521

Molded case circuit breakers
Hide thumbs Also See for 3VA1 100 A:
Table of Contents

Advertisement

Rated peak withstand current, impulse short-circuit current
Maximum permissible instantaneous (peak) value of the prospective short-circuit current in
the current path under the highest load. It characterizes the dynamic short-circuit strength of
a switching device.
Rated residual current
The rated residual current
operated circuit breakers are designed. The residual current rating is declared on the rating
plate of the device.
Rated service short-circuit breaking capacity
The rated service short-circuit breaking capacity
the operational voltage that a molded case circuit breaker is capable of interrupting
repeatedly (test sequence 0 - C0 - CO, formerly P - 2). After a molded case circuit breaker
has interrupted a short circuit, it can continue to carry the rated operational current despite
increased self-heating and will trip again in the event of a short circuit.
Rated short-circuit breaking capacity
The rated short-circuit breaking capacity
current that the circuit breaker can safely interrupt at a specific rated operational voltage and
rated frequency. It is specified as an rms value.
With AC molded case circuit breakers, the rated short-circuit breaking capacity must be
independent of the magnitude of the DC component. The rated short-circuit breaking
capacity also ensures that the molded case circuit breaker can interrupt every current up to
the rated short-circuit breaking capacity in the event of a line-frequency recovery voltage with
110% of the rated operational voltage.
This applies:
● To alternating current at every value of the power factor, but not lower than the value
defined in the relevant test specification.
● To direct current (unless otherwise specified by the manufacturer) with every time
constant, but not greater than the value defined in the relevant test specification.
The short-circuit breaking capacity does not apply in the event of a recovery voltage at line
frequency above 110% of the rated operational voltage.
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
I
is the fault (residual) current for which residual current-
Δn
I
cs
I
of a molded case circuit breaker is the maximum
cn
is the short-circuit current determined by
Glossary
521