&RPPLVVLRQLQJ
6WDUWXS RI WKH '3 PDVWHU V\VWHP
Customize the start-up monitoring time for DP slaves in parameter 0RQLWRULQJ WLPH IRU
SDUDPHWHU WUDQVIHU WR PRGXOHV.
That is, the DP slaves must start up within the set time and be configured by the CPU (as
DP master).
352),%86 DGGUHVV RI WKH '3 PDVWHU
For the DP CPU, you must QRW set  as a PROFIBUS address.

&RPPLVVLRQLQJ WKH &38 DV '3 6ODYH
5HTXLUHPHQWV IRU FRPPLVVLRQLQJ
• The DP master is configured and programmed.
• If the MPI/DP interface of CPU 317-2 DP is to be operated as DP interface, you
must configure the interface accordingly.
• Prior to commissioning, you must assign and configure the DP CPU as a DP
slave. That is, in 67(3  you must:
"switch on" the CPU as DP slave,
assign a PROFIBUS address to the CPU,
assign a slave diagnostic address to the CPU,
specify whether the DP master is an S7 DP master or another DP master,
specify the address areas for data exchange with the DP master.
• All other DP slaves are programmed and configured.
&URVVUHIHUHQFH
Information on changing over to a CPU 31xC, 312, 314, 315-2 DP, and 317-2DP
can be found in the applicable section in the &38 'DWD [& DQG [ Reference
Manual
9-26
&38 [ '3  [& '3 LV D '3 PDVWHU
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03